Protego BR

FA-I-FC

Flame Arrester Unit for installation in devices

Features

Varios tamaños
Disponible para tuberías de DN 50/2" hasta DN 800/32"
Diferentes series
Permite aumentar el tamaño del disco FLAMEFILTER® para una determinada conexión de brida, lo que se traduce en una menor pérdida de carga a través del equipo
Diseño modular
Permite la sustitución y limpieza de los discos de filtro FLAMEFILTER® de forma individual
Piezas de recambio
Piezas de recambio eficientes en costes
Function and Description

Protection Against Atmospheric Deflagrations, Volume Deflagrations, and Engines

The PROTEGO® FA-I-FC Flame Arrester Unit are components installed on or within equipment (e.g. blowers) and have to be tested and approved with this equipment for the respective operating conditions of use. It consists of a FLAMEFILTER® cage filled with FLAMEFILTER®. The FLAMEFILTER® cages are sized so that they can be installed between flange connections. The component provides equipment manufacturers protection against deflagrations, volume deflagrations or protection of engines.

Main Component – PROTEGO® Flame Arrester Unit

Each Flame Arrester Unit is selected from a modular system that provides each manufacturer the option of using optimized, adapted, and cost-effective protection. Our expert technical staff will assist you with the proper selection of the devices as well as execution of type testing.

For All Explosion Groups and Special Gases

The FA-I-FC Flame Arrester Unit consists of two FLAMEFILTER® (1) installed within the FLAMEFILTER® cage (2). The FLAMEFILTER® diameter and gap size depend on the intended use. FA-I-FC components can be arranged for all explosion groups and special gases such as Ethylene oxide.
Product Data

Dimensiones

DN50 / 2"80 / 3"100 / 4"150 / 6"200 / 8"250 / 10"300 / 12"350 / 14"400 / 16"500 / 20"600 / 24"800 / 32"1000 / 40"1200 / 48"1400 / 56"1600 / 64"2000 / 80"
a - 135 / 5.31 155 / 6.10 194 / 7.64 248 / 9.76 310 / 12.20 363 / 14.29 420 / 16.54 465 / 18.31 555 / 21.85 655 / 25.79 855 / 33.66 1070 / 42.13 1280 / 50.39 1500 / 59.06 1700 / 66.93 -
b - 90 / 3.54 110 / 4.33 172 / 6.77 225 / 8.86 285 / 11.22 331 / 13.03 380 / 14.96 430 / 16.93 515 / 20.28 615 / 24.21 815 / 32.09 1015 / 39.96 1215 / 47.83 1415 / 55.71 1615 / 63.58 -
c - 50 / 1.97 50 / 1.97 55 / 2.17 65 / 2.56 - 70 / 2.76 - 70 / 2.76 70 / 2.76 70 / 2.76 80 / 3.15 90 / 3.54 90 / 3.54 110 / 4.33 110 / 4.33 -
d - - - - - 76 / 2.99 - 86 / 3.39 - - 75 / 2.95 85 / 3.35 95 / 3.74 95 / 3.74 115 / 4.53 115 / 4.53 -

Dimensiones en mm / pulgadas

Selection of FLAMEFILTER® gap

FLAMEFILTER® gap
0.9 m / 0.7 mm
0.5 mm
0.3 mm
0.2 mm

If you have any questions regarding the selection of the FLAMEFILTER® (number and gap width), our trained specialists will be happy to advise you.

Material selection for flame arrester unit

DesignABC
FLAMEFILTER® cageSteelStainless steelHastelloy
GasketPTFEPTFEPTFE
FLAMEFILTER® SetA
A
C

Special materials upon request

Combinación de materiales para la unidad apagallamas

Design ACD
FLAMEFILTER® *Stainless steelStainless steelHastelloy
SpacersStainless steelStainless steelHastelloy

* the FLAMEFILTER® is also available in the materials Tantalum, Inconel, Copper, etc. when the listed cage materials are used.

Special materials upon request