FA-G-IIA1-P2.2
In-Line Deflagration Flame Arrester for biogas, sewage gas and landfi ll gas, concentric design, bidirectional, endurance burning proof (under atmospheric conditions)

Features
Diseño modular
Montaje y desmontaje más rápido
Conexión roscada
Transmisión bidireccional de la llama
Proporciona seguridad
Piezas de recambio

Protection of Fuel Supply Lines

For Explosion Group IIA1 - Methan

Many Individual Certifications
Dimensiones
To select the nominal size (DN), use the flow capacity charts on the following pages
| DN | G ½ | G ¾ | G 1 | G 1 ¼ | G 1 ½ | G 2 |
| a | 80/3.15 | 80/3.15 | 100/3.94 | 100/3.94 | 155/6.10 | 155/6.10 |
| b | 55/2.16 | 55/2.16 | 76/2.99 | 76/2.99 | 124/4.88 | 124/4.88 |
| c | 100/3.94 | 100/3.94 | 110/4.33 | 110/4.33 | 170/6.69 | 170/6.69 |
| d | — | — | -— | — | 400/15.75 | 400/15.75 |
| SW | 32/1.26 | 32/1.26 | 50/1.97 | 50/1.97 | 75/2.95 | 75/2.95 |
Dimensions in mm / inches, SW= width across flats
Selección del grupo de explosión
| MESG | Expl. Gr. (IEC / CEN) |
| ≥ 1,14 mm | IIA1 |
Special approvals upon request
Selección de la máxima presión de operación
| Expl. Gr | DN | G ½ | G ¾ | G 1 | G 1 ¼ | G 1 ½ | G 2 |
| IIA1 | Pmax | 2,2/31.9 | 2,2/31.9 | 2,2/31.9 | 2,2/31.9 | 2,2/31.9 | 2,2/31.9 |
Pmax = maximum allowable operating pressure in bar / psi absolute, higher operating pressure upon request
Especificación de la máx. temperatura de operación
| ≤ 60°C / 140°F | Tmaximum allowable operating temperature in °C |
| - | Designation |
higher operating temperatures upon request
Selección de materiales
| Design | B | C |
| Housing | Stainless Steel | Hastelloy |
| Gasket | PTFE | PTFE |
| FLAMEFILTER®* | Stainless Steel | Hastelloy |
* the FLAMEFILTER® is also available in the materials Tantalum, Inconel, Copper, etc. when the listed housing materials are used.
Special materials upon request
Tipo de conexión
| Pipe thread DIN ISO 228-1 | DIN |
other types of thread upon request
Diagrama de flujo volumétrico

Los diagramas de flujo volumétrico han sido determinados con un banco de pruebas de caudal calibrado y certifi - cado por TÜV. El flujo volumétrico V. en [m³/h] y el CFH se refi eren a las condiciones estándar de referencia de aire según ISO 6358 (20°C, 1bar). La conversión a otras densidades y temperaturas están referidas en el Vol. 1: “Fundamentos Técnicos”.