FA-I-V, FA-I-P
Flame Arrester for vacuum pumps, compressors and blowers

Features
Opciones de aplicación versátiles
Diversos usos posibles
Diseño modular
Permite la sustitución y limpieza de los discos de filtro FLAMEFILTER® de forma individual
Piezas de recambio
Piezas de recambio eficientes en costes
Function and Description

Against the Propagation of Explosions
PROTEGO® FA-I-V and FA-I-P Flame Arresters are specifically designed for vacuum pumps, blowers, and compressors. The high flow velocity in the small gaps of these machines can lead to undesirable ignitions within the housing. One of the safest measures against explosion propagation are Flame Arrester Unit that are installed on the vacuum and pressure side of the equipment.
Unique Modular System for Optimized Flame Arresters
PROTEGO® FA-I-V devices for the vacuum side and PROTEGO® FA-I-P devices for the pressure side provide a unique modular design that gives every manufacturer of vacuum pumps or comparable devices the option of using optimized and adapted Flame Arresters. Our expert technical staff will assist you with the proper selection of the devices as well as execution of type testing.

Main Component – PROTEGO® Flame Arrester Unit
PROTEGO® FA-I-V and FA-I-P devices are symmetrical in design. The arrester essentially consists of two housing parts (1) and the PROTEGO® Flame Arrester Unit (2) in the center. The PROTEGO® Flame Arrester Unit is modular and consists of several FLAMEFILTER® (3) and spacers firmly held in a FLAMEFILTER® cage. The number of FLAMEFILTER® and their gap size depends on the arrester´s conditions of use. PROTEGO® FA-I-V and FA-I-P Flame Arresters are available for explosion groups IIA to IIC (NEC groups D to B) and special gases such as Ethylene oxide.
Product Data
Dimensiones
Dimensiones en mm / pulgadas
Selección del grupo de explosión
| FLAMEFILTER® gap | MESG | Expl. Gr. (IEC / CEN) | Gas Group (NEC) |
| 0.7 mm | > 0.90 mm | IIA | D |
| 0.5 mm | ≥ 0.65 mm | IIB3 | C |
| 0.3 mm | ≥ 0.50 mm | IIB | C |
| 0.2 mm | < 0.50 mm | IIC | B |
Selección de materiales para la vivienda
| Design | A | B | C |
| Housing | Steel | Stainless steel | Hastelloy |
| Gasket | PTFE | PTFE | PTFE |
| Flame arrester unit | A, B | B | C |
The housing can also be delivered in steel with an ECTFE coating.
Special materials upon request
Combinación de materiales para la unidad apagallamas
| Design | A | C | D |
| FLAMEFILTER® cage | Steel | Stainless Steel | Hastelloy |
| FLAMEFILTER®* | Stainless Steel | Stainless Steel | Hastelloy |
| Spacers | Stainless Steel | Stainless Steel | Hastelloy |
* the FLAMEFILTER® is also available in the materials Tantalum, Inconel, Copper, etc. when the listed housing and cage materials are used.
Special materials upon request
Tipo de bridas de conexión
| EN 1092-1; Form B1 |
| ASME B16.5 CL 150 R.F. |