Protego BR

VD/TS

Pressure/Vacuum Relief Valve atmospheric deflagration-proof

Features

10% Technology
for Minimum Pressure Increase up to Full Lift
Extreme Tightness
Resulting in Lowest Possible Product Losses and Reduced Environmental Pollution
Optimum Pressure Maintenance
Based on 10% Technology, Set Pressure Is Close to Opening Pressure for Optimum Pressure Maintenance in the System as Compared to Conventional 40% or 100% Technology
Guided Valve Pallet
Valve Pallet Is Guided Inside the Housing to Protect Against Harsh Weather Conditions
Protective System According to ATEX
can Be Used as a Protective System in Areas With Potentially Explosive Atmosphere in Accordance With ATEX
Intergrated Flame Arrester
Integrated PROTEGO® Flame Arrester Unit Saves Space and Weight and Reduces Costs
Flow Capacity
Optimized Flow Capacity
Sturdy Housing Design
(PN 10 and PN 16)
API Tanks
Best Technology for API Tanks
Function and Description

Combined Pressure and Vacuum Relief Valve

The Atmospheric Deflagration-Proof VD/TS Type PROTEGO® valve is a highly developed combined pressure/vacuum relief valve for high flow capacities with an integrated Flame Arrester Unit. It is primarily used as a device for flame transmission proof in-breathing and out-breathing on tanks, containers, and process equipment. The valve offers reliable protection against overpressure and vacuum, prevents the in-breathing of air and product losses almost up to the set pressure, and protects against atmospheric deflagration. The PROTEGO® Flame Arrester Unit is designed to achieve minimum pressure drop with maximum safety. The PROTEGO® VD/TS device is available for substances from explosion groups IIA to IIB3 (NEC group D to C MESG ≥ 0.65 mm).

10%-Technology

When the set pressure is reached, the valve starts to open and reaches full lift within 10% overpressure. This unique 10% technology enables a set pressure that is only 10% below the maximum allowable working pressure (MAWP) or maximum allowable working vacuum (MAWV) of the tank. After years of development, this typical opening characteristic of a safety relief valve is now also available for the low pressure range. The tank pressure is maintained up to the set pressure with a tightness that is above the normal standards due to our state-of-the-art manufacturing technology.

Custom Materials

This feature is ensured by valve seats made of high quality stainless steel and with individually lapped valve pallets (1), or with an air cushion seal (2), in conjunction with high quality FEP diaphragm. The valve pallets are also available with a PTFE seal to prevent them from sticking when sticky substances are used and to enable the use of corrosive fluids. After the overpressure is released, the valve re-seats and provides a tight seal.

Main Component – PROTEGO® Flame Arrester Unit

If the set pressure is exceeded, explosive gas/product vapor/air mixtures are released into the atmosphere. If this mixture ignites, the integrated PROTEGO® Flame Arrester Unit (3) prevents flame transmission into the tank. The standard design is tested at an operating temperature up to +60°C / 140°F and meets the requirements of European Tank Design Standard EN 14015 (Appendix L) and ISO 28300 (API 2000). In addition, numerous versions for higher operating temperature are available. EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.
Product Data

Dimensions

To select the nominal size (DN), please use the flow capacity charts on the following pages

DN50 / 2" 80 / 3" 100 / 4" 125 / 5" 150 / 6" 200 / 8" 250 / 10" 300 / 12"
a340 / 13.39430 / 16.93490 / 19.29610 / 24.02610 / 24.02705 / 27.76765 / 30.12930 / 36.61
b210 / 8.27280 / 11.02310 / 12.20390 / 15.35390 / 15.35445 / 17.52505 / 19.88560 / 22.05
c206 / 8.11277 / 10.91347 / 13.66427 / 16.81427 / 16.81534 / 21.02604 / 23.78823 / 32.40
d125 / 4.92150 / 5.91180 / 7.09230 / 9.06230 / 9.06270 / 10.63310 / 12.20445 / 17.52

Dimensions in mm / inches

Selection of explosion group

MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
≥ 0,65 mmIIB3C

Special approvals upon request

Specification of max. operating temperature

≤ 60°C / 140°FTmaximum allowable operating temperature in °C
-Designation

higher operating temperatures upon request

Material selection for housing

Design  ACDE
Housing Aluminium Steel Stainless Steel Hastelloy
Valve seats Stainless Steel Stainless Steel Stainless Steel Hastelloy
Gasket PTFE PTFE PTFE PTFE
Weather hood
Stainless Steel
Stainless Steel
Stainless Steel Hastelloy
Flame arrester unit A A A C
Pressure valve pallet A-F A-F A-F G-I
Vacuum valve pallet A-E A-E A-E F-H

Special materials upon request

Material combinations of flame arrester unit

Design AC
FLAMEFILTER® cageStainless SteelHastelloy
FLAMEFILTER®Stainless SteelHastelloy

Special materials upon request

Material selection for pressure valve pallet

Design ABCDEFGHI
Pressure range [mbar]
[inch W.C.]
+3.5 up to +5,0
+1.4 up to +2.0
>+5.0 up to +14
>+2.0 up to +5.6
>+14 up to +35
>+5.6 up to +14
>+35 up to +50
>+14 up to +20
>+14 up to +35
>+5.6 up to +14
>+35 up to +50
>+14 up to +20
+3.5 up to +5,0
+1.4 up to +2.0
>+5.0 up to +14
>+2.0 up to +5.6
>+14 up to +35
>+5.6 up to +14
Valve palletAluminiumStainless SteelStainless SteelStainless SteelStainless SteelStainless SteelTitaniumHastelloyHastelloy
SealingFEPFEPMetal to MetalMetal to MetalPTFEPTFEFEPFEPMetal to Metal
WeightStainless SteelStainless SteelStainless SteelLeadStainless SteelLeadHastelloyHastelloyHastelloy

Special material as well as higher set pressure upon request

Material selection for vacuum valve pallet

DesignABCEFGH
Vacuum range [mbar]
[inch W.C.]
-2.0 up to -3.5
-0.8 up to -1.4
<-3.5 up to -14
<-1.4 up to -5.6
<-14 up to -25
<-5.6 up to -10
<-14 up to -25
<-5.6 up to -10
-2.0 up to -3.5
-0.8 up to -1.4
<-3.5 up to -14
<-1.4 up to -5.6
<-14 up to -25
<-5.6 up to -10
Valve palletAluminiumStainless SteelStainless SteelStainless SteelTitaniumHastelloyHastelloy
SealingFEPFEPMetal to MetalPTFEFEPFEPMetal to Metal
WeightStainless SteelStainless SteelStainless SteelStainless SteelHastelloyHastelloyHastelloy

Special material as well as higher set vacuum upon request

Flange connection type

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.

other types upon request

Flow Capacity Chart

The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). For conversion to other densities and temperatures refer to Sec. 1: “Technical Fundamentals”.

Detail X

Detail X